Product Features of FIRSTFLEX TM Nitrile Rubber Copper Pipe Insulation for HVAC:
1). Closed cell structure, least moisture intrusion.
2). Low thermal conductivity, big energy saving.
3). Great fire performance, extra safety and protection.
4). CFC/HFC/HCFC free, dust free & fiber free, ideal for green building.
5). Superior flexibility, easy installation.
6). Added UV resistance, great outdoor performance.
Overview of FIRSTFLEX TM Nitrile Rubber Copper Pipe Insulation for HVAC:
FIRSTFLEX TM Flexible Foam Rubber Insulation Pipe is designed for the insulation of large surfaces, ideal for the insulation of pipes of large diameters. By reducing the number of sections required they simplify installation, saving on time and labor costs.
Facing: Pipe can be covered with aluminum foil and adhesive paper.
Advantages of FIRSTFLEX TM Nitrile Rubber Copper Pipe Insulation for HVAC:
Easy for installation; Moisture resistance; Fiber-free elastomeric foam; Manufactured without use of CFCS or HCFCS; Excellent anti-steam permeated ability; Closed structure can effectively prevent thermal conduction.
Packing:
Packed in Carton; We can make OEM packing.
Application of FIRSTFLEX TM Nitrile Rubber Copper Pipe Insulation for HVAC:
For condensation prevention and energy loss limitation where pipes and ducts, chillers and air conditioning equipment are required;
Efficiently reduces heat flow on hot systems, duct work, large piping, tanks and fittings.
Specifications of FIRSTFLEX TM Nitrile Rubber Copper Pipe Insulation for HVAC:
Outer Diameter of Seamless Tube | DN of Galva-nized Tube | Inner Diameter | 9mm thickness (1.8m/piece) | 15mm thickness (2m/piece) | 20mm thickness (2m/piece) | 25mm thickness (2m/piece) | 30mm thickness (2m/piece) | ||||||
(mm) |
| (mm) | Specif-ication (mm×mm) | pcs/ bag | pcs/ bag | speci-fication (mm×mm) | pcs/ bag | Specif-ication (mm×mm) | Pcs/ bag | Speci-fication (mm×mm) | pcs/ bag | Specifi-cation (mm×mm) | |
|
| 6 | 6×9 | 180 | 180 |
|
|
|
|
|
|
| |
| 6 | 10 | 10×9 | 140 | 140 | 10×15 | 80 | 10×20 | 70 |
|
|
| |
|
| 13 | 13×9 | 120 | 100 | 13×15 | 80 | 13×20 | 50 |
|
|
| |
14 | 8 | 16 | 16×9 | 100 | 95 | 16×15 | 60 | 16×20 | 50 |
|
|
| |
|
| 19 | 19×9 | 100 | 80 | 19×15 | 60 | 19×20 | 40 |
|
|
| |
22 | 15 | 22 | 22×9 | 100 | 70 | 22×15 | 60 | 22×20 | 40 | 22×25 | 30 | 22×30 | |
25 |
| 25 | 25×9 | 80 | 55 | 25×15 | 60 | 25×20 | 30 | 25×25 | 25 | 25×30 | |
28 | 20 | 28 | 28×9 | 60 | 50 | 28×15 | 50 | 28×20 | 30 | 28×25 | 25 | 28×30 | |
32 |
| 32 | 32×9 | 60 | 45 |
|
|
|
|
|
|
| |
32 |
| 34 |
|
|
| 34×15 | 40 | 34×20 | 30 | 34×25 | 25 | 34×30 | |
| 25 | 35 | 35×9 | 60 | 40 |
|
|
|
|
|
|
| |
|
|
| 38×9 | 50 | 30 |
|
|
|
|
|
|
| |
| 25 | 42 | 42×9 | 50 | 30 |
|
|
|
|
|
|
| |
| 32 | 43 | 43×9 | 50 | 30 | 43×15 | 30 | 43×20 | 25 | 43×25 | 20 | 43×30 | |
| 40 | 48 | 48×9 | 50 | 28 | 48×15 | 30 | 48×20 | 25 | 48×25 | 20 | 48×30 | |
|
| 54 | 54×9 | 50 | 25 |
|
|
|
|
|
|
| |
| 50 | 60 | 60×9 | 50 | 20 | 60×15 | 30 | 60×20 | 20 | 60×25 | 15 | 60×30 | |
76 | 70 | 76 |
|
|
| 76×15 | 25 | 76×20 | 15 | 76×25 | 15 | 76×30 | |
89 | 80 | 89 |
|
|
|
|
| 89×20 | 15 | 89×25 | 15 | 89×30 | |
108 |
| 108 |
|
|
|
|
| 108×20 | 15 | 108×25 | 10 | 108×30 |
Technical Parameters of FIRSTFLEX TM Nitrile Rubber Copper Pipe Insulation for HVAC:
Property | Performance | Standard |
Material | NBR/PVC | - |
Cell Structure | Closed Cell | - |
Temperature limits (°C) | -40 °C to +120 °C | - |
Density Range | 40kg/m3 -7Okg/m3 | ASTM D1667 |
Thermal Conductivity ( 40˚C) | 0.038 W/mK | ASTM C518 |
Water Absorption | 2.98 | ASTM D 3575-91 |
Water Vapour Permeability | 0.19 Perm - in | ASTM E 96-95 |
Resistance to Ozone | Excellent | ASTM D 1149 |
Flammability | Self Extinguishing | ASTM D 635-91 |
Fire Performance | Class 0 | ASTM E-84 |
Copper corrosion | Negligible | ASTM C665 |
Limited Oxygen Index | 32% | ASTM D 2863 - 77 |
Fungi Resistance | Passed | ASTM G21/C1338 |
Flexibility | Excellent | ASTM D 1056-85 |